In this section of the working project of the CS, the power unit premises are equipped with fire alarm and notification systems. The notification system is selected as type l in accordance with NPB 104-03.
In accordance with NPB 88-2001*, NPB104-03, NPB110-03, the following is provided for installation:
• smoke fire detectors type IP212-ZSU in the electrical panel room, acid room, KTP premises and in the corridor;
• heat fire detectors IP103-4/1-70-IB "MAK-1IB" inside the battery room, the explosion and fire hazard category of which is A/B-1a; and in the vestibule, the explosion and fire hazard category of which is A/B-16;
• manual fire alarms with safety signs on the outer wall of the building at a height of 1.5 m;
• sound alarms in the building;
• light and sound alarm on the building facade.