Content: 00062_Проект пожарной сигнализации склада ГСМ.rar (525.90 KB)
Uploaded: 21.10.2024

Positive responses: 0
Negative responses: 0

Sold: 0
Refunds: 0

$0.4
In this section, the fire alarm and notification systems are installed in the premises of the building "Pumping station of the fuel and lubricants warehouse".
This section develops a fire alarm system for the premises of the building "Pumping station of the fuel and lubricants warehouse":
• oil pumping station;
• diesel fuel pumping station;
• oil warehouse in containers;
• filter regeneration;
• electrical panel.
The fire alarm system of the fuel and lubricants warehouse allows:
• timely detection of the source of fire;
• generation of a fire signal and transmission to the Orion automated workplace with duplication to the CS dispatcher;
• activation of the notification system;
• shutdown of the process equipment.
The building is equipped with a type 1 notification system in accordance with NPB104-03.
Probable sources of fire are - electrical wiring, faulty electrical equipment.
In accordance with NPB88-2001, NPB104-03, the following shall be installed in the building:

• IP103-4/1-70-IB thermal fire detectors in the diesel fuel pump room, included in the intrinsically safe circuit of the BIV unit of the UPKOP135-1-1 device, connected to the Signal-20P control panel according to a diagram that allows recognizing the operation of two sensors in the intrinsically safe circuit;
• IP 212-ZSU smoke fire detectors in other rooms, except for the foam concentrate warehouse;
• manual fire alarms with safety signs on the outer wall of the building;
• a light and sound alarm on the outer wall of the building and sound alarms inside.

File format: dwg, tif (AutoCAD 2010 not editable)
Note: source files in *.tif format must be in the same folder with the project file *.dwg

Download file "Fire alarm project for fuel and lubricants warehouse" >>>