Content: 00044_Проект электрического отопления КТП АВО газа.rar (198.85 KB)
Uploaded: 07.10.2024

Positive responses: 0
Negative responses: 0

Sold: 0
Refunds: 0

$0.4
The design of the KTP AVO gas heating provides for electric heating, 10 PET-9 furnaces with a capacity of 1 kW each are accepted for installation; which provide an internal air temperature of 5 ° C
To heat the workplace during repair work, 2 VEN-6 electric heaters with a capacity of 6.0 kW each are provided.
Solutions for ventilation of the KTP AVO gas:
1. KTP ventilation is supply and exhaust. In summer, the inflow is natural through louvered grilles, the exhaust is mechanical with two axial fans.
The calculation is made based on heat emission from the equipment.

In winter, ventilation is natural through louvered grilles.
Automation of ventilation of the KTP AVO gas:
The design provides for automatic switching on of the furnaces at t = 5 ° C, and switching off at t = 8 ° C.
Provision is made for switching off the fans in case of fire.

File format: dwg, tif (AutoCAD 2010 not editable)
Note: source files of *.tif format must be in the same folder with the project file *.dwg

Download file "Project of electric heating of KTP AVO gas" >>>

Tags: gas compressor station, AVO gas
No feedback yet